Primary-Secondary Balancing Valve Location
I am investigating a low hot water flow issue for a single building served by a district heating plant. The pumping system is designed as a constant speed primary distribution with varible speed pumps serving the building loads. A three way mixing valve maintains the building loop temperature. The building loop is decoupled from the primary hot water system via an open flow path. The constant volume primary system is regulated with a balancing valve downstream of the decoupler/building return point of connection. This balancing valve maintains primary loop flow. However, during building use, it appears that the decoupler could have reverse flow even at flows less than system design. Since the balancing valve is downstream of the decoupler point of connection, if the pressure is higher in the building return than the supply line (possible with the pump energy added at the building), the flow is reversed. Is this a possible issue that I should study? My initial thought is that if the balancing valve was in the decoupler line, then this would essentially create the pressure drop that the system requires to work properly. Reverse flow would be less likely.
In reviewing the ASHRAE Systems and Equipment handbook, the balancing valves in Fig. 19 appear to be shown in the position that is currently installed in this building and not in the decoupler (common pipe). Is there a reason why it does not get installed in the decoupler?
The decoupler line needs to have as little pressure drop as possible in order to decouple completely. You sometimes see a check valve in these lines to prevent backflow; the disadvantage of that is the check valve's pressure drop.
It would definitely be helpful to see a visual, but you explain it well.
The three-way is not on the decoupler line, correct? In other words,
there are two crossover lines, one being the decoupler and one being the
three-way line to the secondary pump inlet?
It sounds like this
system is misapplied, causing the central plant to move much more water
than it has to. If all buildings have decoupler lines, I can see why
they put a circuit setter at each building. This setup will cause full
(and excessive) plant flow all the time and probably not enough
differential pressure to meet individual buildings' demands.
Primary/secondary
decoupled flow is great for a single building with say, three boilers.
Each boiler can have its fixed primary flow and the secondary pumps can
vary speed to meet building demand.
But for multiple buildings, I
would suggest that they look into getting rid of the decoupler
philosophy and putting check valves on the decoupler lines (preventing
direct supply to return flow at each building), so that the volume of
primary hot water delivered can vary. This would help each building meet
demand.
The three way line should also be done away with and
replaced with a simple return deny valve at each building, where the
balancing valve you mention is currently located. The return deny valve
can be throttled down to ensure return temperature is below 150