Wiring Slow Operating Valves on a Geothermal Heat Pump.
With the costs of fuel (any fuel) still heading skyward, the idea of
"free" energy from the ground is a reality more and more households are
cutting their teeth on. Geothermal systems cost upwards of $7000 to
$20000 depending on the features and if this is an open (pump and dump)
or a closed loop system. Because closed loop systems require a lot of
plumbing run in the ground, these are very expensive, especially for
someone changing from another fuel type (In the city, with a municipal
water supply you will HAVE to use a closed loop per codes if they even
permit a geothermal heat pump at all. This system will dump water in the
sewer system if installed open loop). For those in the country or a
private well, an open loop or pump and dump makes sense. The cost is
relatively low and there's a lot less plumbing to get it going. Pump and
dumps use water from the well to either extract or absorb heat from the
ground. This is because most groundwater is about 55 degrees and even
though it seems cold in the winter, has quite a bit of heat (even frozen
water has heat, but would never make it through the system).
This
is a pretty simple setup. The heat pump is plumbed into the water supply
via pipes with a manual valve on the ingoing side an one or two valves
on the outgoing side, depending on whether or not it's single or two
stage unit. Two stages will have a straight pipe with a loop attached
with a valve on the loop and one on the straightaway. The first stage
will always be on the straightaway and the second stage will be on the
loop. In theory, the first stage valve will open when the thermostat
calls for heat and stay open, even when the thermostat calls for second
stage. Simple huh? Otherwise the furnace will shut off on low water flow
and the emergency heat will probably come on. Customers hate that.
Now
for the disclaimer. I am not responsible for any damage done to your
furnace as I am not your boss. You MUST READ the instructions on the
valve packaging AND the furnace. Improper wiring or testing
methods can cause personal injury and property damage. You MUST
determine whether or not this is going to work for your application.
Follow any advice at your own risk.
Believe me, I burnt out a
control board and a thermostat trying to fix one of these systems and
the customer wasn't a happy camper. Shut off the power to the unit
before disconnecting or connecting anything and if you must use a
voltmeter, please tape the ends so only the very tip is showing. This is
so you don't introduce high voltage to a low voltage part or pop a
breaker. The geothermal heat pumps I've worked on don't have a fuse for
the board (mainly Water Furnace). You've been warned.
Water hammer is
the sound made when a valve closes suddenly under high pressure. Copper
plumbing seems to be prone to this because there's no give. Because any
action will cause a reaction, shutting off a valve quickly will stop
the water flow, but not bleed off the energy behind it. This is like a
car running into a bridge abutment (hard and sudden) as opposed to
having the brakes bleed off the energy in motion (kinetic energy). Slow
operating valves limit or eliminate water hammer by opening and closing
slowly, bleeding off the energy of the water flow.
But these can be a
nightmare to install if you haven't had any instruction on them.
Several calls to Water Furnace tech support had me wiring these to the
board and contactors, but no dice. The valves didn't open and the
furnace wouldn't operate. The written instructions are also unclear on
this step and will confound the tech at every turn. Personally, I've no
problem with doing the job, but I'm not abreast of the technical jargon
either. I've also learned the more complicated you make something, the
more likely you are to royally screw it up. Such is the case with this
furnace; there was no clear way to wire this beast up.
Or is there?
The valves, made by Taco (pronounced Tayco) have orange power heads and
three terminals, each marked 1, 2 and 3. There's also a schematic on
each valve. Use this schematic to wire them up. Here's how to do it.
What
you'll need is enough three or five wire (18 gauge thermostat wire) to
reach the valves and the terminals on the board. Three is for single
stage and five is for two stage systems. You'll also need three wire
nuts for the two stage and none for the single stage.
Take your wire
and run it into the furnace and loosely place it where you want it where
it's going to away from anything that will damage same. Slit the outer
insulation about 8 inches at each end and peel the wires apart as using a
stripper on the outer casing will nick the wires. Strip off enough of
the inner insulation so you can hook everything up without the bare
wires touching each other. Hook the number 1 terminal (s) on the valve
(s) to the common or "C" on the board. One wire should suffice for both;
use two short pieces and a wire nut to hook up the common wire. Now
this is where it gets tricky. Find out which valve is for first stage,
hook one end to the number 2 terminal. Hook the other end of this wire
to the "Y1" ("Y" if it's a single stage) taken from the board. Then hook
another free wire to the 3 terminal on the valve and hook that to the
"Y" terminal on the board. Do the same with the stage two valve, using
the remaining wires to hook up the 2 terminal to the "Y2" wire from the
thermostat and terminal 3 to the "Y2" terminal on the board.
What
happens is the thermostat calls for heat, or cooling and sends power to
the valve, which opens and sends power to the contactor, which turns the
compressor on. Numbers 1 and 2 on the valve actually supply the path to
operate the valve, while numbers two and three are connected to a micro
switch and no power goes between them. These are known as "dry"
contacts for that reason. This wire completes the circuit to the board
from the thermostat when valve is finished opening. Viola! it should be
pumping heat in no time. Maranatha!
MORE NEWS